Model 4734 Access Control Expander Installation Manual (P/N 150807, Rev. A) Revised 5/98
38
AUTO NO FRC:NO (4)
When selected, Auto Close will cause alarms on any Not Ready Zones.
AUTO OC:--------
Enter areas that will Auto Open or Auto Close.
AREA NAME#1:
Select a name for each area being used (16 characters maximum). Area names are displayed
when accessing area arming and with the zone status to show which area the zone is in. (Areas
were programmed in ZONE OPTIONS, Menu 8.) The factory programmed default names are
A1 - A8.
OP WIN GRP #1
Select the window group number (programmed in Menu 11) that will control opening this area.
Use #32 for always, #33 for never.
CL WIN GRP #1
Select the window group number that will control closing this area.
5.17.1 Open/Close Groups
Open and Close Window Groups are available for each area. It is possible for eight areas to
arm and disarm at different times. It is also possible for one or more areas to Auto-Arm and
one or more areas to report OPEN/CLOSE TROUBLE on the same system. Each area can be
programmed as auto arm, auto disarm, or open/close trouble.
5.17.2 Exception Reporting
This mode controls reporting of open/close activity. Exception reporting applies when an area
is assigned a time window group which includes inactive periods (not always inside a window)
and Report Exception open/close is selected. When the arming occurs within an active period
of the close window group, the arming does not report to the central station. When the arming
occurs outside the windows, the arming is reported to the central station. Likewise, open
reporting is controlled by the open window group.
5.17.3 Open/Close Trouble
This mode causes trouble reports to be sent when Manual Opening or Closing does not occur
during the specified open and close window groups. The report is sent at the end of an active
period of the window group. Open Trouble (system still open) is sent when the system is not
closed (armed) at the end of a close window period. Close Trouble (system still closed) is sent
when the system is not opened (disarmed) at the end of a open window period.
Open/Close Trouble and Exception Open/Close may be combined by selecting both.
5.17.4 Auto Open/Close
This mode causes an area to automatically arm or disarm at the end of an active period in a
time window group. Auto Open/Close is selected as an option for each area. If, at the end of a
close window period the area is not armed, the area is then automatically armed.
Auto Open/Close may be combined with Exception Open/Close Operation. Auto Open/Close
disables Open/Close Trouble Reports for the area.
5.18 Sensor Locations (Menu 17)
SENSOR#1:
Enter a location description for each of the four sensors used with the 4150 Auxiliary Control
(16 characters maximum).