Model 4734 Access Control Expander Installation Manual (P/N 150807, Rev. A) Revised 5/98
26
DAY TRBL#1:NO
If this option is selected, the zone will be supervised only while the zone is disarmed. Day trou-
ble loop response is always .062 seconds. Day Troubles will not restore, until silenced from a
touchpad. Typical day trouble zones are window foils or emergency exits. If you select DAY
TRBL for a zone, you must also select N.C. for that zone. Do NOT pick both 24HR TRBL and
DAY TRBL.
24HR TRBL#1:NO
Select this option for any zone that will be supervised 24-hours a day, such as a fire zone (all
supervised zones require 15 K ohm EOL).
24-hour trouble loop response is always 10 seconds. A 24-hour trouble will restore as soon as
the loop is restored. Do NOT pick both 24HR TRBL and DAY TRBL.
N.C.#1:NO
Select this option if the zone will be using normally closed contacts (all N.C. zones require a
15 K ohm EOL).
N.O.#1:YES
Select this option when the zone will be using normally open contacts.
NO EOL:NO
Select NO if you are using an end-of-line (EOL) resistor. Select YES if you are not using an
EOL resistor.
SPEED#1:06s
This option determines the speed at which the zone will respond to an alarm condition. Select
the number shown next to the desired zone response speed in the following table.
24HR#1:NO
Select this option if the zone will be monitored for alarm conditions 24-hours a day (for exam-
ple, if it is a fire, emergency or tamper zone).
EXIT#1:NO
Select this option if the zone will have an exit delay time or if it is an interior zone that is in the
exit corridor.
ENTRY1#:NO
The system has two separate entry delay times. Select this option if the zone will be controlled
by Entry Delay #1.
ENTRY2#:NO
Select this option if the zone will be controlled by Entry Delay #2.
Table 8: Loop Response Times
Selection # Loop Response Time
0
1
2
3
0.010 seconds
0.062 seconds
1 second
10 seconds