Model 4734 Access Control Expander Installation Manual (P/N 150807, Rev. A) Revised 5/98
27
INTERIOR:NO
Interior zones can be bypassed as a group using the INT key. Select this option if the zone will
be an interior zone.
BYPASS#1:NO
Select this option if you want to be able to bypass (shunt) the zone. If you do not select this
option for a particular zone, you will not be able to bypass that zone.
NOTE Fire zones must NOT be bypassable.
CHIME#1:NO
This option enables the chime function for a particular zone. When the chime function is
enabled, the CHM key can be used to turn a door chime on and off when the system is dis-
armed.
AREA#1:1
Key in the number of the area to which you want to assign the zone. A zone can be assigned to
only one of eight areas.
TYPE#1:FIRE
Enter the number corresponding to the desired zone type in the following table.
NOTE 1. Undefined, Water, Heat, Cold, and Local zones will display as Auxiliary on the LCD. If
Local is selected, the panel will not dial out.
2. Do not select the “Unused” (zone type 14 or 15) zone type. It is intended for future use by
the factory. Use option 12 “Unused” if you need to program a zone that does not cause an
alarm.
3. Option 6 was changed from “Gas” to “Supervisory” with Revision C of the 4734-2 control
software.
4. When programmed as zone type Unused or Door Bell and 24-hour zone, the zone will not
affect the ready light. This allows Door Bell zones to be not ready when the system is armed.
Unused zones may be used as inputs to programmable I/O without affecting the system.
LOCATION#1
For this option, enter a 16-character location description of Zone 1, such as BEDROOM or
GARAGE. See Section 4.5 of this manual for instructions on entering text.
Table 9: Zone Types
Selection # Zone Type Selection # Zone Type
0 HOLDUP 8 WATER
1 FIRE 9 HEAT
2 EMERGENCY 10 COLD
3 PANIC 11 LOCAL
4 BURGLARY 12 UNUSED
5 TAMPER 13 DOORBELL
6
SUPERVISORY
(formerly GAS)
14 UNUSED
7 UNDEFINED 15 UNUSED