Regency
®
Model 4734 Access Control Expander Installation Manual (P/N 150807, Rev. A) Revised 5/98
23
NO PULS BELL:NO
Select yes for steady fire bell output. (Used for strobes.)
5.7 Access Options (Menu 6)
REP DG:NO (report door access granted)
This option causes the system to send a report indicating that the door was accessed using a
valid code number. The event is also printed.
DOOR DISARM:NO
This option causes the areas assigned to a particular access code to disarm automatically when
door access is granted to that access code.
NOTE This option is effective only if the code has been programmed with the capability to disarm
(PROFILES, Menu 2).
REP/PR EXIT:NO
This option causes all door exit events to be printed and reported to the central station. Exit
requests are printed and reported as DOOR ACCESS ID 0.
PR DOOR:NO
This option causes all door access events to be printed.
NOTE If you also select REP DOOR (ACCOUNTS, Menu 9), door access events will be printed and
reported to the central station.
REP DO/DF:NO (report door open/door forced)
Selecting this option causes the system to send a report every time the door sensor is violated
without using door access. It will report if the door is forced open or left open.
REP DOOR RST:NO
Select to report DOOR RESTORE events to the central station. This option requires a 9000
receiver upgrade.
REP ACC DEN:NO
Select to report ACCESS DENIED events to the central station. This option requires a 9000
receiver upgrade.
HIDE CODES:NO
If this option is enabled, users cannot see all codes when programming new codes. Codes with
programming ability can change secret codes, but they will see “*****” in place of the digits
of the code. This feature applies only to codes 2-255. When the Code 0 and Code 1 are used to
program codes, the digits of the code(s) will display. (This option is new with the 4734-2,
Revision C2 or later.)
5.8 Dialer (Menu 7)
COMP PH
If you will be using the downloading feature, you must enter the phone number that the com-
puter will be connected to. The number entered may be up to 16-digits long.